EATON – ZB32-XEZ – Electromechanical Relays – ICDC-041049 – New
Main Category: Electromechanical | Sub-Category: Relays | Status: New Original Components
EATON Part Number: ZB32XEZ | ICDC Internal Part Number: ICDC-041049
ZB32-XEZ Description:
ZB32-XEZ – Socket for separate installation, for thermal relay ZB32
278473
SUPPLY PROGRAM
Assortment
Accessories
accessories
Plinth
Function
For separate installation
use with
ZB32
Note
Snap-mountable on an IEC / EN 60715 DIN rail or screw fasteners.
For ZB32-38 use BK25 / 3-PKZ0 in addition.
TECHNICAL DATA
Main circuit
Rated impulse withstand voltage [U imp ] 6000 V AC
Overvoltage category / pollution degree
III/3
Rated insulation voltage [U i ] 690 V
Rated operational voltage [U e ] 690 V AC
Safe isolation according to EN 61140
Among the main contacts themselves
440 V AC
Connection sections
Stiff
1 x (1-16)
2 x (1-16) mm2
Connection sections
Flexible with ferrule
1 x (1-4)
2 x (1-4) mm2
Connection sections
Single wire or stranded
18-8 AWG
Connecting screw
M4
Connecting screw tightening torque
1.8 Nm
Stripping length
10 mm
Tools
Pozidriv screwdriver
2 Size
Tools
Flat-blade screwdriver
1 x 6 mm
DESIGN VERIFICATIONS ACCORDING TO IEC / EN 61439
Technical data for design checks
Rated operational current for dissipation data [I n ] 38 A
Dissipation per pole, as a function of the current [P vid ] 0.1 watts
Device dissipation, depending on the current [P vid ] 0.3 watts
Static dissipation, independent of the current [P vs ] 0 W.
Dissipation power [P ve ] 0 W.
Ambient service temperature min.
-25 °C
Ambient service temperature max.
+55 °C
IEC / EN 61439 design verifications
10.2 Suitability of materials and components
10.2.2 Corrosion resistance
The requirements of the product standard are met.
10.2 Suitability of materials and components
10.2.3.1 Resistance of the enclosure to heat
The requirements of the product standard are met.
10.2 Suitability of materials and components
10.2.3.2 Resistance of insulating materials to normal heat levels
The requirements of the product standard are met.
10.2 Suitability of materials and components
10.2.3.3 Resistance of insulating materials to extraordinary heat levels
The requirements of the product standard are met.
10.2 Suitability of materials and components
10.2.4 Resistance to UV radiation
The requirements of the product standard are met.
10.2 Suitability of materials and components
10.2.5 Lifting
Not relevant as the whole electrical panel needs to be evaluated.
10.2 Suitability of materials and components
10.2.6 Impact test
Not relevant as the whole electrical panel needs to be evaluated.
10.2 Suitability of materials and components
10.2.7 Lettering
The requirements of the product standard are met.
10.3 Degree of protection of the enclosures
Not relevant as the whole electrical panel needs to be evaluated.
10.4 Airborne and superficial dispersion routes
The requirements of the product standard are met.
10.5 Protection against electric shock
Not relevant as the whole electrical panel needs to be evaluated.
10.6 Flush mounting of devices
Not relevant as the whole electrical panel needs to be evaluated.
10.7 Internal circuits and connections
It is the responsibility of the manufacturer of the electrical panel.
10.8 Connections for conductors introduced from outside
It is the responsibility of the manufacturer of the electrical panel.
10.9 Insulation characteristics
10.9.2 Mains frequency dielectric strength
It is the responsibility of the manufacturer of the electrical panel.
10.9 Insulation characteristics
10.9.3 Impulse withstand voltage
It is the responsibility of the manufacturer of the electrical panel.
10.9 Insulation characteristics
10.9.4 Verification of enclosures in insulating material
It is the responsibility of the manufacturer of the electrical panel.
10.10 Heating
The superheat calculation is the responsibility of the electrical panel builder. Eaton provides equipment dissipation data.
10.11 Resistance to short circuit
It is the responsibility of the manufacturer of the electrical panel. Observe the default values of the equipment.
10.12 EMC
It is the responsibility of the manufacturer of the electrical panel. Observe the default values of the equipment.
10.13 Mechanical function
For the device, the requirements are met if the information in the installation instructions (IL) is observed.
TECHNICAL DATA ACCORDING TO ETIM 8.0
low voltage electrical appliances (EG000017) / Accessories for overload element (EC002027)
Technique Of Ar., Electr., Energy, Tecn. For Comm., Network & Mains Process / Low Voltage Switching Technology / Overload Protection / Overload Protection (accessories) ([email protected] [ACO017011])
accessory type
base
Accessory
Yes
Spare part
no
APPROVALS
Product Standards
UL 508
Contact us to discover ZB32-XEZ. ICDCSPARES.COM offers new or overhauled original components, ready in stock to be shipped via DHL Express! Call us!
Check our Electromechanical section to discover more about ICDC catalog: a large selection of industrial spare parts including Fuses, Electric Motors, Switches and Relays.
Are you looking for industrial Relays?